T&R PT30-10 mk3 High Voltage DC Cable Test System
The T&R PT30-10 high voltage dc test sets are designed to perform tests on installed cable and jointing systems. The units have a variable output voltage with a maximum or �30kVdc (PT30-10). The PT30-10 have a maximum charging capability of 10mA.
A zero-volt interlock is fitted that prevents the output being switched on unless the output control is at zero.
T&R PT30-10 mk3 features:
- �30kVdc output voltage
- 10mA output capability
- Both voltage and current metered on HV outputs
- Automatic earth system for dumping capacitive loads
- HV output plug & socket system
- Key operated supply switch to prevent unauthorised operation
- Zero-volt interlock
- Visual indication of test piece failure
- Automatic mains voltage selection
The units include an automatic load discharge system that discharges the cable under test when the output is switched off or a breakdown occurs. The internal dumping system can discharge a maximum of 2.5kJ on each output, corresponding to 4?F at 30kV.
In the event of a test object failure, the overload circuit will automatically switch off the output voltage and earth the output via the internal discharge circuit. A manual discharge probe is also supplied as standard with both units, allowing higher load capacitances to be safely discharged. The mk2 units introduce automatic 115/230V mains voltage selection, allowing easy transition between site voltages.
The output voltage is metered by two large, linear, analogue instruments marked 0-30kV (PT30-10). Test object current is metered by two further analogue instruments with 0-10 scale marking. The meters read 0-10mA directly, or 0-1mA when the �10 push button is operated. The HV output from the unit uses a high quality plug and socket system, allowing for easy cable replacement.
Supplied with
- Operating manual
- Calibration certificate
- Mains lead
- Spare fuse
- Keys
- Carry case
- Lead bag
- 5m HV output leads
- 5m earth lead
- DP40 discharge probe